How is the air pressure regulated for Guangdong purification projects

2023-07-11 1309

For most clean spaces, in order to prevent external pollution from entering, it is necessary to maintain an internal pressure (static pressure) higher than the external pressure (static pressure). The maintenance of pressure difference should generally comply with the following criteria:

The pressure in a clean space should be higher than that in a non clean space.

2. The pressure in spaces with high cleanliness levels should be higher than that in adjacent spaces with low cleanliness levels.

The maintenance of pressure difference relies on the fresh air volume, which should be able to compensate for the air leakage from gaps under this pressure difference. So the physical meaning of pressure difference is the resistance of air leakage (or infiltration) through various gaps in the clean room.

广东净化工程

Rules for airflow velocity in clean rooms

The airflow velocity to be commented on here refers to the airflow velocity in the clean room, and the airflow velocity in other clean spaces will be explained when commenting on the detailed equipment.

Regarding turbulent flow cleanrooms, the concept of air exchange rate is mainly used to reduce indoor pollution by relying on the dilution effect of air, rather than directly using the concept of velocity. However, there are also requirements for indoor airflow velocity;

(1) The airflow velocity at the outlet of the air supply outlet should not be too high. Compared with a simple air-conditioned room, it is required that the velocity decay be faster and the dispersed viewpoint be larger.

(2) The velocity of the airflow blowing through the horizontal plane (such as the backflow velocity during side feeding) should not be too high to avoid blowing surface particles back into the airflow and causing re pollution. This velocity should generally not be too high at 0.2m/s.

Regarding parallel flow cleanrooms (commonly known as laminar flow cleanrooms), the speed on the cross-section is a very important target because it mainly relies on the "piston kneading effect" of the airflow to clean up impurities. In the past, the US 20GB standard was used, which adopted 0.45m/s. However, people also understand that such high speeds require a large amount of ventilation, and in order to save energy, the feasibility of reducing wind speed is also being explored.

In China, both the "Technical Measures for Clean Air" and the "Design Specification for Cleanrooms" have such rules

Vertical parallel flow (laminar flow) clean room ≥ 0.25m/s

Horizontal parallel flow (laminar flow) clean room ≥ 0.35 m/s